Cooling tower characteristics


BVG 36



градирня купить
2БВГ 36


градирня купить

градирня купить градирня купить градирня купить
Buy now

градирня купити градирня купити градирня купити

Name of the parameterMeasuring unitValue
Operation conditions
Performance on waterm3/hour130-400
Type of irrigatorCombined(Film + net layer)
Temperature of incoming water°СNot more than 65
Temperature of cooled water°Сt* + (4÷6)
Temperature difference, Δt°С5÷20
Thermal load at Δt = 10°СkW1520 ÷ 4660
Droplet entrainment%≤0,01
Pressure in water distribution systemМCE2021-05-03 00:00:00
Standard of thermal calculationCTI ATC 105
Cooling tower construction
Type of the cooling towercontra-flow exhaust
Number of sectionspcs1
Arrangement of sectionsliner
Dimensions of cooling tower (width, length)m3,6х7,2
Total height of cooling towerm5.1
Height of water distribution systemm2.8
Height of air inlet windowsm0.97
Height of diffuserm0.6
Number of clamping shoulders of water inlet, Dуmm4x150
Irrigation aream225.92
Fan installation
Number of fanspcs.1
Brand of electromotorАСВО5К
Type of connection between motor and fanDirect drive
Fan diametermm2400
Material for bladesfiberglass
Rotation rateprm.485
Noise level (10 meters from cooling tower)dB65
Parameters of electromotorV/Hz/F380/50/3
Nominal power of electromotorkW2х(9-13)
Electromotor protectionIP54
Insulation classF

ComponentMaterial
BodyHot dipped galvanized steel
Fan stackFRP
CasingFRP
FillPVC / PP (upon request)
Drift eliminatorPVC / PP (upon request)
PipesFRP
Nozzles PP / ABS (upon request)
Air guidesPP / Galvanized steel
Fan instalationPAG (blades), AI (hub)
Fan supportHot dipped galvanized steel
Connecting elementsCink Steel
Water trayFRP
Fan protectionCink Steel
Motor housingColor coated steel

  • Low running costs
  • Minimum maintenance requirements
  • A wide range of components to best meet the requirements of the Customer
  • Optimal weight for positioning on overlapped buildings
  • The shortest possible installation and commissioning time
  • Thermal design of the cooling tower, structural design, selection of materials and components are performed in accordance with technical requirements. Only the highest grade materials and mechanical equipment are used in the construction of the cooling tower, the reliability of which has been proven over time. The final optimal design solutions are a combination of modern methods based on computer technology.
  • The frame of the cooling tower consists of metal structures, assembled on site. All internal and external metal structures of the cooling tower are treated with a special high-performance anti-corrosion coating. The roof of this cooling tower consists of four segments made of glass fiber reinforced polyester and is installed at an angle, thus forming a confuser.
  • Polymer sprinkler provides a high water cooling effect at low aerodynamic resistance, does not clog, and is resistant to low air temperatures. A fan unit is located in the upper part of the cooling tower, providing air supply. The fan unit includes an impeller with plastic blades, a diffuser and an electric motor.
  • To ensure optimal operation of the electric motor and the fan unit itself, depending on atmospheric parameters and the temperature of the chilled water, the cooling tower is equipped with a control and monitoring system with a frequency-controlled electric drive, which significantly reduces power consumption. The water distribution system is made of plastic.
  • The cooling tower is delivered in separate assembly units by road and is assembled on site. Installed on a previously prepared pool or tied to an existing one. Installation time of a cooling tower on a prepared pool is 4-7 days.
  • Может быть выполнена модификация градирни с стеклопластиковым каркасом.
Cooling towerHeat load.Hydraulic
load
Cooling tower dimensionsMotorFan diameterInlet connectionTransport weight.Weight
Model kW m3/h.L, W, H, mm. kWmm.Dn, mmkg.kg.
BVG-362.9002503600х3600х4950 92.400150х23.50011.400
BVG-403.5003004000х4000х4950132.400150х23.85013.600
BVG-423.8503304200х4200х4950152.400150х24.00014.450
BVG-805.22010008000х8000х690037(55)4.500300х218.00025.000
2 BVG-365.8005007200х3600х49509х22.400150х46.75022.200
2 BVG-407.0006008000х4000х495013х22.400150х47.25026.640
2 BVG-427.7006608400х4200х495015х22.400150х47.80029.050
3 BVG-368.75075010800х3600х49509х32.400150х69.85032.980
3 BVG-4010.50090012000х4000х495013х32.400150х610.50039.600
 3 BVG-4211.600100012600х4200х495015х32.400150х611.00046.640